Description
LIFASA automatic capacitor banks are used for centralized
compensation of power factor in low voltage installations.
These equipments are supplied completely assembled and
ready for use: it is only necessary to connect it to the mains
with cables of adequate cross section, and to supply the
operation signal from a suitable current transformer.
General CharaCteristiCs
LIFASA automatic capacitor banks are composed of the following elements:
High rupturing capacity (HRC) fuses connected to a busbar
system.
Contactors specially adapted to the work with capacitors.
Inrush current limiting inductances.
Fast discharge resistors.
Low losses power capacitors.
Reactive power controllers.
Terminals for neutral and ground conductors.
Metal cabinet containing all the switchgear..
Advantages
Equipments wired and tested at works, full finished and
supplied with all control and safety devices.
Easy transportation and installation due to their light weigh.
Easy selection of the most appropriate cos φ to avoid penalty charges on tariffs.
Long life and high reliability, thank to the use of self-healing and low losses capacitors.
Wide range of power (from 5 to 1600 kvar, 440 V) with
standard equipments for immediate delivery.
Option of including various accessories.
Technical characteristics
Tensiones nominales/Rated voltages…………230 / 440 /690 V
Frecuencia nominal/Rated frequency…………50 Hz - 60 Hz
Potencia nominal/Rated power…………5 ... 1600 kvar
Pérdidas dieléctricas/Dielectric losses…………< 0.2 W/kvar
Pérdidas en los condensadores/Capacitors…………losses < 0.5 W/kvar
Sobretensión máxima/Maximum overvoltage…………1.1 Un (8h/dia/day)
Sobreintensidad máxima/Maximum overcurrent…………1.3 In
Resistencia de descarga rápida/Fast discharge resistors…………En cada contactor/On each contactor
Equipo de regulación/Regulation equipment…………Reguladores MCE ADV o PFCL Elite/MCE ADV or PFCL Elite controller
Programas de trabajo/Working programs…………1:1:1:1 / 1:2:2:2 / 1:2:4:4 /1:2:4:8 / 1:1:2:2
Tensión de maniobra/Control voltage…………230 V
Conexión transformador de intensidad/External current transformer………… /5 (Opcional/Optional)
Gama climática/Temperature range…………-23oC/+45 oC max. temp.
Grado de protección/Degree of protection…………
Instalación/Installation…………Interior/Indoor
Normas/Standars…………, , ,
Special Equipment
On request, automatic capacitor banks
can be produced to customers special requirements. Among the different
possibilities are the following:
Other voltages and frequencies.
Capacitor banks with different degrees of protection.
Capacitor banks for outdoor installation.
Working program 1:2:4:4:, 1:2:4:8:,
1:1:2:2:.
Fixed step (for transformer compensation).
Higher powers than the above stated.
BATLV400 150-400 kvar
AUTOMATIC CAPACITOR BANK
c aracterísticas técnicas /t eChniCal CharaCteristiCs
Tensión nominal/Rated voltages....................440 V 50 Hz - 60 Hz
Regulador/Controller ......................................MCE ADV
Programa trabajo/Working program .............5 opciones/options
Condensador/Capacitors ...............................Tipo/Type FML
Protección/Protection steps ............................Fusibles/Fuses NH00
Grado IP/Degree of protection ...................
Color/Colour .....................................................Gris/Grey RAL 7035
Instalación/Installation ....................................Interior/Indoor
Montaje/Assembly ...........................................Sobre suelo/
Floor mounting
Dimensiones/Dimensions .................................650x460x1900mm
a ccesorios /a CCessories
Interruptor general de corte en carga ó automático /
Main switch or Circuit breaker
Protección diferencial / Leakage protection
Part number |
Qn (kvar)
440 V |
Composition |
Steps |
Program |
Qn (kvar)
400 V |
(kg)
Weight |
()
Price |
BATLV4044150 |
150 |
2x25+2x50 |
6x25 |
1.1.2. |
124 |
195 |
4.701 |
BATLV4044175 |
175 |
25+50+100 |
7x25 |
1.2.4. |
145 |
195 |
4.829 |
BATLV4044187 |
187.5 |
12.5+25+50+100 |
15x12.5 |
1.2.4.8. |
155 |
200 |
4.956 |
BATLV4044200 |
200 |
50+50+100 |
4x50 |
1.1.2. |
165 |
200 |
5.135 |
BATLV4044225 |
225 |
25+50+50+100 |
11x25 |
1.2.2.4. |
182 |
205 |
5.56 |
BATLV4044250 |
250 |
50+2x100 |
5x50 |
1.2.2. |
207 |
208 |
6.037 |
BATLV4044275 |
275 |
25+50+2x100 |
11x25 |
1.2.4. |
227 |
210 |
6.539 |
BATLV4044300 |
300 |
50+50+2x100 |
6x50 |
1.1.2. |
248 |
215 |
7.015 |
BATLV4044350 |
350 |
50+3x100 |
7x50 |
1.2.2. |
289 |
220 |
7.492 |
BATLV4044400 |
400 |
4x100 |
4x100 |
1.1.1. |
330 |
225 |
8.568 |
Other ratings, voltages and frequencies available on request.
BATLV400
BATLV4044150 BATLV4044250
BATLV4044175 BATLV4044275
BATLV4044187 BATLV4044300
BATLV4044200 BATLV4044350
BATLV4044220 BATLV4044400
|